MP82710-H (ATEX)

MP82710-H (ATEX)
MP82710-H (ATEX)
MP82710-H (ATEX)
Hart®
MP82710-H (ATEX)
MP82710-H (ATEX)
MP82710-H (ATEX)
MP82710-H (ATEX)

Mp82710-H (ATEX) features
• Microprocessor based
• RTD, T/C, mV and Ohm input
• Fully linearized & infallibly galvanically isolated
• RFI / EMI protected
• High accuracy (Typical 0.1%)
• Hart® communication
• Optional plug-in readout & head
• ATEX approval available
• 5 Year warranty


Order Information

Example:
Model Mp82710H –D-CW-IF-EX

Options:
-D = Plug-in Loop-powered Readout
-CW = DAN type connection head with window
-IF = Interface and software
-EX = Intrinsically Safe Approval
ATEX Ex II 1 G Ex ia IIC T4...T6 Ga

General
Cold junction drift ± 0.01°C/°C
Input Ohm Ohm, mV
Input RTD Pt100, Pt250, Pt500, Pt1000, Ni100, Ni500, Ni1000, Cu10, Cu100
Input T/C K,J,L,T,U,E,R,S,B,C,D,N
Isolation 500 VDC / 1500 VAC
Linearization On / Off
Supply Effect 0.001%/V
Other inputs Ohm, mV
Supply 5..40 VDC, Polarity Protected
Long Term Drift ± 0.05%/Year
Output 4..20 mA or 20..4 mA and Hart® protocol
Excitation Current, RTD 0.1 mA
Load capability Vbat-10V / 20 mA
Sensor Lead Resistance, RTD 500 Ohm max.
Zero drift ± 0.01%/°C or ±0.02°C/°C
Sensor Lead Resistance, T/C 10,000 Ohm max.
Span drift ± 0.005%/°C or ±0.01°C/°C
Ambient Operating Temp. -40...+ 85°C.
Open Circuit Detection Upscale / Downscale
Ingress Protection IP30
Startup Time ± 10 sec.
Storage Temperature -40...+100°C.
Warmup Time ± 5 Min.
Housing Material Zinc Alloy (ZAMAK 5) epoxy coated
Housing Dimensions 43mm Dia. x 27mm H. (1.70” x 0.99”)
Housing Dimensions with Read-Out 47mm Dia. x 36mm H. (1.85” x 1.42”)