ALM42
ALM42 features
• Analogue transmitter
• Free scalable (solder link + potentiometers)
• Available for Pt100 (RTD), thermocouple K,J or T or mV input
• High accuracy (typical 0.2%)
• Rugged epoxy coated housing
• Temperature linear output (Pt100 version)
• Voltage linear output (T/C version)
• 5 Year warranty
Order details (example)
Model
ALM42-R Input Pt100
ALM42-T-K Input T/C K
ALM42-T-J Input T/C J
ALM42-T-T Input T/C T
ALM42-mV Input mV
General | |
Power supply | 14 – 40 VDC |
Power supply effect | 0.002%/V |
Polarity protected | Yes |
Output | 4 – 20 mA |
Load capability | (V[bat] – 14 V) / 20 mA |
Sensor burn out | Upscale (max. 35 mA) |
Zero drift | ± 0.025%/°C |
Span drift | ± 0.010%/°C |
Ambient Operating Temp. | -20...+80°C |
Ingress Protection | IP30 |
Storage Temperature | -40...+100°C |
Housing Material | Zinc Alloy (ZAMAK 5) epoxy coated |
Housing Dimensions Dia. x H | 43 mm x 29 mm (1.70” x 1.14”) |
Pt100 | |
Span adjustment Pt100 | 50 to 800°C |
Zero adjustment Pt100 | -50 to +50°C |
Linearization | 0.1% |
Sensor lead effect | 0.03°C/Ohm |
Max. sensor line resistance | 250 Ohm |
Thermocouple | |
Range T/C K | 0 to 1200°C |
Range T/C J | 0 to 900°C |
Range T/C T | 0 to 400°C |
Zero adjustment T/C | -25 to +50°C |
Span adjustment T/C | T/C K: 150 to 1200°C T/C J: 150 to 600°C T/C T: 150 to 400°C |
Cold junction drift | 0.03°C/°C |
Max. sensor line resistance | 10,000 Ohm |
mV | |
Range | 0 to 160 mV |
Minimum span | 10 mV |